| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2016 | FRODRIG2 | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Completed | |
| 07/08/2016 | FRODRIG2 | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Approved | |
| 07/12/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the size and serial number of the existing water meter serving this building. Show the total demand served by the meter. 2. Provide the size of the backflow preventer associated with the water meter. |
| 07/12/2016 | MARTIN BROWN | FIRE | REVIEW | Needs Review | MANUAL FIRE ALARM SYSTEM IS REQUIRED PER IFC/IBC SECTION 907.2.2. NO INDICATION THAT IT IS EXISTING OR PROPOSED ON THE DRAWINGS -KEN B. |