Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM04628
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2016 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T16CM04628 - PLAN REVIEW COMMENTS: 2nd Review Reviewer: Chris Anderson, December 12, 2016 BUILDING – COMMERCIAL Per response to previous comments 2 – 4 changing ramp to an exterior area for assisted rescue: Show a 48” clear width for the stairs between railings on detail 7/A-412 per IBC 1007.7.6. On Door Schedule, sheet A-801, door 104 must be 1-hour fire-rated per 1007.7.4 and Table 716.5. Existing door must either bear a label identifying it as such, or provide new fire-rated door. Add sign to interior side of door 104 “EXTERIOR AREA FOR ASSISTED RESCUE” per 1007.9. Per response to previous comment 6, revise the added note to include “0.83” as the U-factor for entry doors and add “operable fenestration shall have a maximum U-factor 0.65 with SHGC of 0.25.” Per response to previous comment 7, the point-of-sale added detail 19/A-903 does not match millwork MW2 shown on the first floor plan, sheet A-210. Explain. |
| 12/13/2016 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL Response to previous note 2 says “please see attached load calculations.” No heating and cooling load calculations were submitted. Per previous comment, “the output capacity of heating and cooling equipment and systems shall not exceed the loads calculated in accordance with Section C403.2.1.” Ref, IECC C403.2.1 and C403.2.2. Submit load calculations with summary sheets showing that scheduled heating and cooling equipment comply. Per response to previous comment 3, and to prevent inadvertent recirculation of restroom air into the restaurant space should the fan not be manually turned on when the restroom is occupied, provide a 7-day programmable time wall switch, scheduled to operate during operating hours, or other means to satisfy the requirements of subscript g on IMC Table 403.3. |
| 12/13/2016 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2016 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL The response to previous comment 2 “Design Team will seek exception via RWRD” brings no resolution at this time, therefore the plumbing plan as shown in the documents cannot be approved. Resubmit with resolution from RWRD, Industrial Wastewater. |
| 12/15/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Steve Shields, Principal Planner PROJECT: T16CM04628 178 E. Broadway Blvd. New Food Service TRANSMITTAL: December 15, 2016 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Provide the Design Review Board (DRB) case number, T16SA00355, adjacent to the title block on the cover sheet. Provide a general note on the cover sheet stating the DRB case number, date of approval, what was approved and any conditions of approval on the cover sheet. The plans will need to be stamped by DRB prior to approval. 3. Sheet A-001 provide a access lane width dimension from the proposed stairs to the parking space to the west. Per UDC Table 7.4.6-2 the minimum width for a one-way access lane is 10', plus per UDC Article 7.4.6.F.2.b an additional 2' setback is required to the proposed stair area. 4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. |
| 12/19/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved |