Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The specified faucet for lavatory LV-1 (Delta Lahara T2738) is not a metering faucet as required. [Initial comment: Provide an automatic faucet for the new public lavatories located in the child care restroom, the sales floor restroom, and the poolside restroom. The faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]
2. The specified wall box for the clothes washers (Guy Grey Model FRIB12ABSHA) is actually a wall box for an ice maker connection. [Initial comment: Clarify if the replacement of the four combination washer/dryers will require any modification to the water piping or waste piping serving the appliances. Reference: Section 107.2.1, IBC 2012.]
09/16/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/22/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved