Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM04599
Parcel: 12218280B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04599
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2016 MARTIN BROWN FIRE REVIEW Approved
06/30/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide third-party listing and material standards (or manufacturer and model) for all new plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2012.
2. Provide an automatic faucet for the new public lavatories located in the child care restroom, the sales floor restroom, and the poolside restroom. The faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
3. Verify that new lavatories in the child care restroom, the sales floor restroom, and the poolside restroom provide tempered water using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
4. If the new showers do not have pre-fabricated receptors, provide details to show that the construction of the receptors comply with the requirements of Section 417.5.2, IPC 2012.
5. Provide a plumbing design for any of the concealed water supply or drainage piping that will be modified as a result of relocating any of the water closets, lavatories, showers, or sinks. Reference: Section 107.2.1, IBC 2012.
6. Clarify if the replacement of the four combination washer/dryers will require any modification to the water piping or waste piping serving the appliances. Reference: Section 107.2.1, IBC 2012.
06/30/2016 ROBERT SHERRY WATER REVIEW Completed
06/30/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify if the replacement of the four combination washer/dryers will require any modification to the exhaust ducts for the dryers. Reference: Section 107.2.1, IBC 2012.
07/11/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Per the notes on the plan sheets A2.01 thru A4.13. It appears there is electrical work to be performed, such as, the removal and replacement of Lighting, possibly branch circuit wiring to accommodate the removal and replacement or relocation of appliances, receptacles. Therefore please provide complete electrical plans as required per City of Tucson Commercial Plan Submittal Requirements ( www.tucsonaz.gov/pdsd ) and as required by the State of Arizona Revised Statutes 32-125, and R4-30-304.
#2. The current adopted NEC is 2011 not 2005, ( cover plan sheet ).
#3. UNABLE TO COMPLETE THE ELECTRICAL PLAN REVIEW AT THIS TIME.
Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
R4-30-302. Electrical Plans
A. A registrant shall prepare and submit drawings and specifications for a new electrical system or an addition or modification to an existing electrical system provided the service and associated electrical feeders exceeds 600 amperes 120/240 volts, single phase or 225 amperes 120/208 volts, three phase and the fault current exceeds 10,000 amperes.
B. In all cases a registrant shall design:
1. Electrical installations in hospitals or other buildings with surgical operating rooms regulated by Article 517 of the National Electrical code (1990 edition) incorporated herein by reference and on file with the Office of the Secretary of State.
2. Electrical installations in locations classified as hazardous in Article 500 of the National Electrical Code (1990 edition) incorporated herein by reference and on file with the Office of the Secretary of State.
3. Electrical installations in locations classified as hazardous in Article 500 of the National Electrical Code (1990 edition) with the exception of gasoline dispensing or repair garages.
4. A registrant shall design an alarm or signaling system that is required for life safety or code compliance.

Ref:2012 IBC 107.2.1, 2011 NEC
07/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.00; CODE ANALYSIS: PLEASE REVISE THE IBC, IMC, IPC, AND IFGC TO THE 2012 EDITION. THE NEC IS PER THE 2011 EDITION. REMOVE THE 2010 ADA AND REVISE THE ICC/ANSI TO THE 2009 EDITION. VERIFY THE DRAWINGS MEET ALL REQUIREMENTS FOR THE REVISED CODE EDITIONS.
2. SHEET A0.00; SPRINKLER SYSTEMS: PLEASE INDICATE ON THE DRAWINGS THE SPRINKLER SYSTEM TYPE PER THE IBC SECTION 903.3.
3. SHEET A0.01; #5: THE ICC/ANSI SECTION 405.2 INDICATES RAMP RUN SLOPES SHALL BE GREATER THAN 1:20 AND NOT STEEPER THAN 1:12. PLEASE REVISE THE DRAWING AS REQUIRED.
4. SHEET A0.02; #4: THE ICC/ANSI SECTION 607.4.1.2.2 INDICATES A VERTICAL GRAB BAR IS REQUIRED ON THE CONTROL END WALL. PLEASE INDICATE ON THE DRAWINGS.
5. SHEETS A0.05 AND A0.06: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
6. SHEET A2.51; DETAIL 3: THE ICC/ANSI SECTION 608.3.1.2 INDICATES A VERTICAL GRAB BAR IS REQUIRED ON THE CONTROL END WALL. PLEASE INDICATE ON THE DRAWINGS.
7. SHEET A2.51; DETAIL 3: IS THIS TRANSFER TYPE SHOWER (36" X 36") ON THIS PROJECT? IF NOT, PLEASE REMOVE THIS DETAIL OR REVISE AS REQUIRED.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.