Permit Number: T16CM04543
Parcel: 13214001B

Address:
901 E 46TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04543
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A102; ELEVATION 4: THE HEIGHT OF THE COUNTER/SINK MUST BE 2'-10". PLEASE REVISE.
2. SHEET A-101; FLOOR PLAN: PLEASE INCLUDE MORE INFORMATION (OR DETAIL) SHOWING THE DRINKING FOUNTAIN (ACCESSIBLE HEIGHTS, CUPS, ETC.).
3. SHEET A-101; FLOOR PLAN: PLEASE INDICATE THE CLEAR FLOOR SPACE AT THE DRINKING FOUNTAIN MEETS THE CLEAR FLOOR SIZE SPACE INDICATED IN THE ICC/ANSI SECTION 305.3.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/14/2016 ROBERT SHERRY WATER REVIEW Completed
06/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide accessible drinking fountains per Section 410.2, IPC 2012.
06/14/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/15/2016 MARTIN BROWN FIRE REVIEW Approved