Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2017 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM04499
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½"control conduit and two ¾" copper piping for water with rooftop termination; straight 3" capped sleeve; or an accessible attic (clear path 30" wide x 30" high) over the water heater. Show appropriate notation.
2. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". See electrical comments.
3. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Property with 200 to 400 SF of available distribution area requires piping for one gray water fixture, and a property with over 400 SF requires complete compliance. Include a provide gray drain-line discharge of all second story bathing fixtures through an exterior-wall drop for future gravity distribution. Include an aliened purple colored 2" vertical drop to a cleanout cap 2' above grade. The home owner may perform system alteration for future gray water usage. Or, notate "Gray water provision not required only when property has less than 200 SF available for gray water distribution."


SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground (R317.1 item 5) with minimum ½" diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. The weep screed requires a minimum clearance 4" above grade or 2" above paved areas, R703.6.2.1. Update details 1 & 2 sheet A-2 showing the 6" spacing.
2. The plans show an unvented roof assembly, R806.1. Remove the vent notation from the north and south elevations, sheet A-5.

PLUMBING PLANS:

1. See the gray water details at the City of Tucson web site for clarification and compliance. Include the details for the minimum two story configuration at https://www.tucsonaz.gov/pdsd/building-codes under the New! listing, select Residential Gray Water Illustration - Attachment A.

ELECTRICAL PLANS:

1. Update overtyped notation at the left column, sheet E-1.
2. Add a double breaker space for future Photo Voltaic on the panel schedule.
3. Revise the electrical load calculation showing a minimum 3,800 volt-ampere or 16 A continuous load entry for future Photo Voltaic equipment.
4. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.
5. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. The plan shows four unshielded lamps with a rating of 600 lumens each. Lumen calculations are determined using the rated fixture wattage, not the installed lamp wattage. Update the calculation.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review