Permit Number: T16CM04419
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04419
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2016 ANDREW CONNOR ZONING REVIEW Approved
06/09/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/09/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/09/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
06/09/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T.1; OCCUPANT LOAD: PLEASE REVISE THE TOTAL OCCUPANT LOAD TO MATCH THE SALES/NON-SALES CALCULATIONS.
2. SHEET T.1; CONSTRUCTION TYPE: PLEASE USE THE 2012 IBC TO DETERMINE THE COONSTRUCTION TYPE (CHAPTER 6). REMOVE THE UBC REFERENCE.
3. SHEET A.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
4. SHEET A.2; RESTROOM ELEVATION: PLEASE REVISE USING THE 2009 ICC/ANSI A117.1 FIGURES 604.5.1 AND 604.5.2 FOR GRAB BAR LOCATIONS.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/09/2016 ROBERT SHERRY WATER REVIEW Completed
06/09/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/09/2016 MARTIN BROWN FIRE REVIEW Approved
06/09/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2016 RBENT1 OUT TO CUSTOMER Completed