Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM04384
Parcel: 141361510

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM04384
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2016 STEVE SHIELDS ZONING REVIEW Approved
07/11/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
07/11/2016 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/11/2016 RBENT1 OUT TO CUSTOMER Completed