Permit Number: T16CM04296
Parcel: 13317062A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04296
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2016 ANDREW CONNOR ZONING REVIEW Approved
06/08/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Update the registrant seal.
#2. Provide or assign lighting and power branch circuiting and panel schedule.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC art. 408.4
06/08/2016 ACONNOR1 ENGINEERING REVIEW Approved
06/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/08/2016 ROBERT SHERRY WATER REVIEW Completed
06/08/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The population of this suite is in excess of 15 which requires the installation of separate restrooms for each sex. (Section 2902.2, IBC 2012). Section 405.3.2, IPC 2012 requires that the required lavatory be located in the same room as the water closet.
06/08/2016 MARTIN BROWN FIRE REVIEW Approved
06/08/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved