Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM04296
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/08/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 06/08/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Update the registrant seal. #2. Provide or assign lighting and power branch circuiting and panel schedule. Ref: 2012 IBC sec. 107.2.1, 2011 NEC art. 408.4 |
| 06/08/2016 | ACONNOR1 | ENGINEERING | REVIEW | Approved | |
| 06/08/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/08/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/08/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The population of this suite is in excess of 15 which requires the installation of separate restrooms for each sex. (Section 2902.2, IBC 2012). Section 405.3.2, IPC 2012 requires that the required lavatory be located in the same room as the water closet. |
| 06/08/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/08/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved |