Permit Number: T16CM04283
Parcel: 106060180

Address:
1320 W PRINCE RD

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM04283
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Indicate feeder conduit, conductor sizes and types between the meters and the service disconnects.
#2. Verify that the service disconnect for the new house panel is to have only 2 fuses.
Ref: 2012 IBC 107.2.1, 2011 NEC.
06/08/2016 ANDREW CONNOR ZONING REVIEW Approved