Permit Number: T16CM04260
Parcel: 127070580

Address:
5105 E BURNS PL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM04260
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
06/07/2016 ANDREW CONNOR ZONING REVIEW Approved
06/27/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/27/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/29/2016 KEN BROUILLETTE FIRE REVIEW Completed The approved fire sprinkler plans and permit were for a NFPA13D system. This permit indicates that more bedrooms are now proposed and this is not reflected on the fire sprinkler permit. The amount of people getting care will require a NFPA13R system which was previously applied and approved in 2009, but did not get installed. Section 903.2.8.2 of the 2012 IFC allows a NFPA 13D system for care facilities in a dwelling unit with 5 or fewer individuals. The proposed occupant load is 10 which falls into a Group R-4 Occupancy Classification and the fire sprinkler system is required to be installed to NFPA 13R standards per Section 903.3.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2016 CPIERCE1 APPROVAL SHELF Completed
06/29/2016 CPIERCE1 OUT TO CUSTOMER Completed