Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM04253
Parcel: 14041056A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM04253
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2016 KEN BROUILLETTE FIRE REVIEW Approved
06/20/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G.1; CODE REVIEW: PLEASE PROVIDE CALCULATIONS ON THE DRAWINGS FOR THE REQUIRED PLUMBING FIXTURES, INCLUDING WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINKS.
2. SHEET G.1; CODE REVIEW (2a): THE DRAWING INDICATES A 2 HOUR RATED EXTERIOR BEARING WALL. PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS FOR EXTERIOR WALL OPENINGS IN THE IBC SECTION 705.8 ARE MET.
3. SHEET G.1; CODE REVIEW (2a): PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS FOR EXTERIOR WALL PARAPETS IN THE IBC SECTION 705.11 ARE MET.
4. SHEET G.1; CODE REVIEW (2a): PLEASE VERIFY ON THE DRAWINGS THE REQUIRED FIRE RESISTANCE RATINGS FOR EXTERIOR WALLS PER THE IBC TABLES 601 AND 602 ARE MET.
5. SHEET A.1; FLOOR PLAN: THE 2012 INTERNATIONAL PLUMBING CODE SECTION 405.3.2 REQUIRES THE WATER CLOSET AND LAVATORY TO BE IN THE SAME ROOM. PLEASE ADDRESS THIS ISSUE.
6. SHEET A.1: PLEASE INCLUDE ON THE DRAWINGS ENLARGED PLANS OF THE TWO RESTROOMS. INDICATE ALL CRITICAL DIMENSIONS AND CLEARANCES ON THE PLANS REQUIRED BY THE ICC/ANSI CHAPTER 6.
7. SHEET A.1; FLOOR PLAN: PER THE IBC SECTION 1109.11, THE WORK COUNTER HEIGHT (SEE KEYNOTE 17) MUST BE AT AN ACCESSIBLE LEVEL (36"). SEE THE ICC/ANSI SECTION 904.
8. SHEET A.1; KEYNOTES: NOTES 6, 31, AND 33 WERE NOT LOCATED ON THE PLAN. PLEASE VERIFY.
9. SHEET A.3; BUILDING SECTIONS A AND B: THE PARAPETS REFERENCE A DETAIL 3/A.4 IN FOUR LOCATIONS. PLEASE REVISE THAT REFERENCE.
10. SHEET A.3; BUILDING SECTION A: THE FOOTING ON THE LEFT SIDE REFERENCES A DETAIL 3/S.2. PLEASE REVISE THAT REFERENCE.
11. SHEET A.7; ELEVATION 3: PLEASE INDICATE GRAB BARS PER THE ICC/ANSI FIGURE 604.5.1 AND FIGURE 604.5.2.
12. SHEET A.8; LUNCH ROOM COUNTER ELEVATION: PER THE IBC SECTION 1109.3, THE LUNCH ROOM SINK HEIGHT MUST BE AT AN ACCESSIBLE LEVEL (34"). SEE THE ICC/ANSI SECTION 902.
13. SHEET A.8; SERVICE MANAGER'S COUNTER ROOM 108: PER THE IBC SECTION 1109.12.3, THE COUNTER HEIGHT MUST BE AT AN ACCESSIBLE LEVEL (36"). SEE THE ICC/ANSI SECTION 904.
14. SHEET S.0; GENERAL STRUCTURAL NOTES (FOUNDATIONS): PLEASE PROVIDE ONE COPY OF THE SOIL REPORT FOR REVIEW.
15. SHEET S.1; FOUNDATION PLAN: PLEASE SHOW THE COLUMN FOOTING F5 AT THE STEEL COLUMN HSS6X3X 1/4 IN THE WEST BUILDING WALL..
16. SHEET S.1; FOUNDATION PLAN: DETAIL 1/S.1 CUT AT THE MASONRY COLUMN FOOTING IN THE NORTHWEST AREA OF THE PLAN SHOULD BE REFERENCED AS 4/S.1. PLEASE VERIFY.
17. SHEET S.1; FOUNDATION PLAN: DETAIL 4/S.3 CUT AT THE MASONRY COLUMN FOOTINGS (THREE LOCATIONS) ON THE NORTH WALL SHOULD BE REFERENCED AS 4/S.1. PLEASE VERIFY.
18. SHEET S.1; DETAIL 1: A STEP FOOTING NOTE REFERENCES DETAIL 7/S.1. PLEASE REVISE THAT REFERENCE.
19. SHEET S.2 (ROOF FRAMING PLAN); SHEET S.4 (PLANS 4 AND 6): PLEASE REFERENCE PLAN 4 (CANOPY 1) AND PLAN 6 (CANOPY 2) ON THE ROOF FRAMING PLAN.
20. SHEET S.2; KEYNOTES: NOTE 2 REFERENCES DETAIL 15/2.3 FOR BLOCKING/STRAPPING. PLEASE REVISE THAT REFERENCE.
21. SHEET S.2; DETAIL 1: PLEASE MOVE THE BOXED NOTE SO IT IS LEGIBLE, AND INCREASE THE TEXT SIZE TO 3/32" MINIMUM.
22. SHEET S.2; DETAIL 2: PLEASE MOVE THE UPPERMOST TEXT SO IT IS LEGIBLE.
23. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/21/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
06/24/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show how the customers at the facility are able to access the men's restroom if they are not allowed to freely pass through the automobile service area. Reference: Section 403.3.1, IPC 2012.
2. Unlike plumbing fixtures, evaporative coolers impose a continuous demand on the water distribution system. Determine the demand from the evaporative coolers and add it to the fixture demand. Reference: Section A 2.2, UPC 2012.
3. Show the size and route of the T&P relief pipe from the water heater. Reference: Section 504, IPC 2012.
4. Show the size and route of the T&P relief pipe from the water heater. Reference: Section 504, IPC 2012.
5. Specify the vacuum breaker to be installed for the irrigation system. Verify that it is protected from damage caused by freezing. Reference: Sections 608.13.5, 608.14.2, and 608.16.5, IPC 2012.
6. Show the size, route, and termination of the drains for the evaporative coolers. Reference: Section 802.1.5, IPC 2012.
7. The Roof Downspout Calculations shown on sheet A.4 appear to be based on Tables 1106.2 and 1106.3, IPC 2012. The use of these tables is not an appropriate method for determining the size of a scupper. These tables are respectively for determining the size of vertical downspouts and horizontal pipes running full; scuppers are weirs, not pipes and their sizes are hydraulically calculated. In addition, the scuppers drain discrete roof areas of unequal size with different areas of surrounding vertical walls. Reference: Sections 1101, 1106, and 1108, IPC 2012.
06/24/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The pole mounted luminaires, designation 'N' on plan sheet E.0 does not corralate with the lighting fixture schedule.
#2. Indicate lamp color source temerature output for the exterior luminaires for compliance with section 402.1 of the Tucson/Pima County Outdoor Lighting Code.
Ref; 2012 IBC sec. 107.2.1, 2011 NEC.
06/24/2016 ROBERT SHERRY WATER REVIEW Completed
06/24/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.
2. Clarify the different U-values and R-values used in the calculations shown on sheet A.7, the Envelope Compliance Certificate, and the cooling/heating load calculations. Correct the arithmetic, use recognized R-values for the components, and recognize the parallel heat transfer paths. Reference: Section 107.2.1, IBC 2012.
3. Verify that the Solar Heat Gain Coefficients and U-values for the fenestration (sheet A.7) are NFRC-certified. Reference: Section C303.1.3, IECC 2012.
4. Show that specified heat pump has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
5. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
06/28/2016 KROBLES1 ZONING REVIEW Needs Review
06/28/2016 LOREN MAKUS ENGINEERING REVIEW Needs Review