Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T16CM04237
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/15/2016 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Doors with closers require 12" of clearance on the latch side of the opening when approaching from the push side of the door, Section 404, ANSI A117.1. This would seem to conflict with Section 604.9.3.1 which requires a maximum of 4" from the partition. Yet this problem is nonexistent when the door swing matches the figure provided or the compartment is large enough to accommodate the alternate 56" clearance. |
| 07/15/2016 | CLAYTON TREVILLYAN | PLUMBING-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/18/2016 | RBENT2 | OUT TO CUSTOMER | Approved |