Review Details: CELL TOWER/ANTENNAS
Permit Number - T16CM04187
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Please indicate wiring methods used ( conduits, conductors, pull boxes, etc ) to accomplish the relocation of the light pole. #2. Please provide complete compliance with the Tucson / Pima County Outdoor Lighting Code for exterior lighting. Ref: 2012 IBC sec. 107.2.1, 2011 NEC. |
| 06/20/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. STRUCTURAL CALCULATIONS: PLEASE INCLUDE THE DRAWINGS ON THE CALCULATION SHEETS 2, 3, AND 4 ON FULL SIZE DRAWINGS. IN ADDITION, INCLUDE DESIGN CRITERIA, MATERIALS, AND SPECIAL INSPECTIONS ON THE FULL SIZE DRAWINGS. 2. GENERAL: PLEASE PROVIDE A WRITTEN RESPONSE TO THE COMMENT. |
| 07/13/2016 | KROBLES1 | COMMUNICATIONS | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/13/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |