Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM04141
Parcel: 117200270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04141
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2016 CPIERCE1 ZONING REVIEW Approved Approval done by Patricia
06/06/2016 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Completed
06/06/2016 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed
06/06/2016 KEN BROUILLETTE FIRE REVIEW Approved
06/06/2016 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change PLANS REVIEW COMMENTS - T16CM04141
New foundations, steel framing, doors and frames, EIFS exterior wall system, roofing system, and underground plumbing only.
Reviewer: Chris Anderson
SHEET s2.0:
1. Plan 1/S1.0 should be labeled "roof framing plan". Detail markers 202 and 203 appear to be reversed.
SHEET as8.0
1. Detail 2/as8.0 (101/s3.0) indicates a new exterior wall set on an existing concrete slab and the only barrier to prevent water from entering the building is a sealed joint between bottom of EIFS and slab. Because of this the moisture barrier behind the insulation board has no way of draining. Most EIFS systems require a 2" separation between bottom of EIFS and paved areas; and although this new addition could be located far enough under the existing walkway that no driven rain will reach it, perhaps not - especially if the existing slab is sloped such that ponding could occur in this location. Use detail 6/as8.0 (102/s3.0) at all new exterior EIFS walls.
2. There are many existing large exposed pipes running through this area under the existing walkway. Will any penetrate the new EIFS exterior wall system? Is so, provide penetration detail(s).
06/06/2016 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLANS REVIEW COMMENTS - T16CM04141
New foundations, steel framing, doors and frames, EIFS exterior wall system, roofing system, and underground plumbing only.
Reviewer: Chris Anderson


SHEET p1.1:
1. Show drain pipes and sizes for new shower at the Home locker rooms.
2. What are the two clothes washers draining to?
3. Show drain pipes and sizes for the new shower at the UA restroom.
4. Keynote 4 says "New soil line, sizes to be shown in contract documents." These are contract documents for underground plumbing. Please clarify intent.
5. Provide plumbing materials specification.
06/08/2016 CPIERCE1 WATER REVIEW Reqs Change Provide the size of the water meter(s) serving this building, the size of the backflow preventer(s) associated with the water meter(s), and the total water demand served by the water meter(s). Reference: Section 107.2.1, IBC 2012.
06/08/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Provide a site plan showing location of work reletive to overall site and a north arrow. Please also add a note indicating that location of offsite stormwater discharges will not change