Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM04104
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE AREA OF THE NEW CANOPY MEETS THE REQUIREMENTS OF THE IBC SECTION 508.2 FOR ACCESSORY OCCUPANCIES, OR THE NEW CANOPY MEETS THE AREA REQUIREMENTS OF THE IBC SECTION 508.3 FOR NON-SEPARATED OCCUPANCIES.
2. GENERAL: PLEASE INCLUDE DETAILS ON THE DRAWINGS FOR THE NEW FOUNDATIONS, INDICATING SIZE, CONCRETE STRENGTH, AND REINFORCING.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2016 RBENT1 OUT TO CUSTOMER Completed