Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM04104
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/28/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE AREA OF THE NEW CANOPY MEETS THE REQUIREMENTS OF THE IBC SECTION 508.2 FOR ACCESSORY OCCUPANCIES, OR THE NEW CANOPY MEETS THE AREA REQUIREMENTS OF THE IBC SECTION 508.3 FOR NON-SEPARATED OCCUPANCIES. 2. GENERAL: PLEASE INCLUDE DETAILS ON THE DRAWINGS FOR THE NEW FOUNDATIONS, INDICATING SIZE, CONCRETE STRENGTH, AND REINFORCING. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/29/2016 | RBENT1 | OUT TO CUSTOMER | Completed |