Permit Number: T16CM04099
Parcel: 13213087F

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM04099
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify why a backwater valve is required for Planet Fitness. Floors discharging from a level 12" or more above that the rim elevation of the next upstream manhole shall not discharge through a backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.