Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM04074
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM04074
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change PLEASE REVISE THE INDEX OF DRAWINGS ON SHEET A1.1 DUE TO THE ADDITION OF SHEETS A9.2 AND A9.3.
06/10/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Insulation is required on the first 8-feet of both the supply (CW) and discharge (HW) piping. [Initial comment: If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012.]