Permit Number: T16CM04074
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04074
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2016 ANDREW CONNOR ZONING REVIEW Approved
06/01/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
06/01/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2016 KEN BROUILLETTE FIRE REVIEW Approved
06/02/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A9.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
06/02/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/07/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/07/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater which is located above the fixture outlets. Reference: Section 504.2, IPC 2012.
2. An elevated mop sink is not an approved termination point for the T&P relief from the water heater. Reference: Section 504.6 (6), IPC 2012.
3. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012.
06/07/2016 ROBERT SHERRY WATER REVIEW Completed