Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM04067
Parcel: 13320128A

Address:
602 N WILMOT RD

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM04067
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The branch of the gas pipe that appears to be intended to serve the future gas load of 144 CFH is too small. Based on Table 402.4(2), 2012 IFGC, a 1" pipe with a developed length of 200 feet can only accommodate 134 CFH. [Initial comment: Clarify the future load for the gas piping. The note at the meter locations calls out 288 CFH for the new gas load with only 144 CFH identified on the plumbing plans. Provide the load and developed pipe length that was used to determine the pipe size for the future load.]
2. Current work is required to comply with the currently-adopted codes. See Sections 1101.7, 1106, and 1108, IPC 2012 for roof drainage requirements. Note that scupper sizes cannot be determined using Tables 1106.2 or 1106.3, IPC 2012: scuppers are weirs and capacity calculations are required, especially for round scuppers. [Initial comment: Show how overflow rain drainage is being provided for the revised roof..]