Permit Number: T16CM04067
Parcel: 13320128A

Address:
602 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04067
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2016 ANDREW CONNOR ZONING REVIEW Approved
06/01/2016 LOREN MAKUS ENGINEERING REVIEW Approved
06/01/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2016 KEN BROUILLETTE FIRE REVIEW Approved
06/02/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/02/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/06/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the future load for the gas piping. The note at the meter locations calls out 288 CFH for the new gas load with only 144 CFH identified on the plumbing plans. Provide the load and developed pipe length that was used to determine the pipe size for the future load.
2. Show how overflow rain drainage is being provided for the revised roof.
06/07/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/07/2016 ROBERT SHERRY WATER REVIEW Completed