Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
06/01/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
06/01/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/01/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
06/02/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/02/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/06/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the future load for the gas piping. The note at the meter locations calls out 288 CFH for the new gas load with only 144 CFH identified on the plumbing plans. Provide the load and developed pipe length that was used to determine the pipe size for the future load. 2. Show how overflow rain drainage is being provided for the revised roof. |
06/07/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
06/07/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |