Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T16CM04063
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/27/2016 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T16CM04063 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. Place the seal on sheets a1 - a5. SITE PLAN: 1. Indicate the distance of new or altered buildings from property lines, R106.1.1. Clarify if a the building wall or roof overhang is inside of the required fire separation distance, R302. FLOOR PLANS: 1. Exterior walls with a fire separation distance less than 3-foot require not less than one-hour fire-resistive construction without openings such as windows. If the studio structure is not 3 feet from property line show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value (R-30 for addition <20%). Update detail notes at 4/A5, 8/A5 and 9/A5. PLUMBING PLANS: 1. When specifying a gray drain line with an exterior diverter valve (keynote 11), show a complete collection and discharge system consistent with P3009 for Recycling Systems with a backflow device. 2. Provide devices rated for application, G2406.3. A diverter valve (keynote 12) for drainage may not be located within the building. Show a gray drain line to the building exterior and an exterior diverter valve and appropriate connections. 3. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance. Update the undersized ½" pipe from the meter. 4. Provide a gas (1,000 BTUh = 1 CFH) conversion coordinated with Southwest Gas. ELECTRICAL PLANS: 1. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4. Show the receptacle near the water heater on a different circuit. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/05/2016 | CPIERCE1 | OUT TO CUSTOMER | Completed |