Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM04052
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/03/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/14/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
06/17/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET PV1.30; PV PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CLEAR DISTANCE DIMENSIONS, OR ADD A REFERENCE TO THE PLAN INDICATING TO SEE SHEETS PV1.31 AND PV1.32 FOR ENLARGED DIMENSIONS. 2. STRUCTURAL CALCULATIONS: THE LARSON CALCULATIONS INDICATE THE TOTAL WEIGHT OF THE BALLAST BLOCKS REQUIRED FOR UPLIFT RESISTANCE. WERE THOSE WEIGHTS INCLUDED IN THE SOCORE CALCULATIONS? PLEASE VERIFY. IS THIS THE 6 PSF PV DEAD LOAD INDICATED? PLEASE SHOW ON THE DRAWINGS HOW THE 6 PSF LOAD WAS DERIVED. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
06/22/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide in detail, on the plan documents the wiring methods used to perform the supply side tap in the electrical service equipment, including hardware and materials. The two details provided on plan sheet PV4.00 #3 and #4 seem to be in conflict by #4 showing what appears to be side by side bus on one phase with a gap ? Also provide verification from the manufacturer of the electrical service equipment that this installation will not compromise the listings or performance of the equipment. Or provide for a field evaluation and re- listing of the equipment by a NRTL . Ref: 2012 IBC sec.107, 2011 NEC art. 110.3. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/13/2016 | RBENT1 | OUT TO CUSTOMER | Completed |