Permit Number: T16CM04031
Parcel: 13321075A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM04031
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The revision to detail D-17/MD calls for the cabinet doors to "open clear for H/C access." Indirect waste receptors are to have ready access which is defined as being accessible "without requiring removal or movement of any panel, door or similar obstruction…" Reference: Section 202, IPC 2012. [Second comment: Keynote #3, P1.1 calls for a hub drain to be located inside of the base cabinet for sink S-4.] [Initial comment: Verify that indirect waste receptors will not be installed in inaccessible or unventilated spaces (e.g. cupboards, storerooms, or closets). Indirect waste receptors shall have ready access. Reference: Section 802.3, IPC 2012.]
09/27/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the revised heating/cooling calculations. [Initial comment: Revise the heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.]
10/06/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/11/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2016 LBOJORQ1 APPROVAL SHELF Completed
11/08/2016 LBOJORQ1 OUT TO CUSTOMER Completed
11/08/2016 LBOJORQ1 REJECT SHELF Completed