Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM04031
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The revision to detail D-17/MD calls for the cabinet doors to "open clear for H/C access." Indirect waste receptors are to have ready access which is defined as being accessible "without requiring removal or movement of any panel, door or similar obstruction…" Reference: Section 202, IPC 2012. [Second comment: Keynote #3, P1.1 calls for a hub drain to be located inside of the base cabinet for sink S-4.] [Initial comment: Verify that indirect waste receptors will not be installed in inaccessible or unventilated spaces (e.g. cupboards, storerooms, or closets). Indirect waste receptors shall have ready access. Reference: Section 802.3, IPC 2012.] |
| 09/27/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide the revised heating/cooling calculations. [Initial comment: Revise the heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.] |
| 10/06/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/11/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/08/2016 | LBOJORQ1 | APPROVAL SHELF | Completed |
| 11/08/2016 | LBOJORQ1 | OUT TO CUSTOMER | Completed |
| 11/08/2016 | LBOJORQ1 | REJECT SHELF | Completed |