Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM04031
Parcel: 13321075A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04031
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2016 KEN BROUILLETTE FIRE REVIEW Approved
06/13/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. The use of a bottle filling station in lieu of two accessible drinking fountains will require the installation of drinking cups at an accessible location. Reference: Section 410.2, IPC 2012.
3. All healthcare related fixtures, devices, and equipment (e.g. Ram-Vac) shall discharge to the building drainage system utilizing an air gap, not air break. The Ram-Vac detail appears to show a direct connection to the sanitary waste system. Reference: Section 802.1, IPC 2012.
4. Verify that indirect waste receptors will not be installed in inaccessible or unventilated spaces (e.g. cupboards, storerooms, or closets). Indirect waste receptors shall have ready access. Reference: Section 802.3, IPC 2012.
5. Provide a single, dedicated shut off valve for all of the gas outlets in the lab, located adjacent to the egress door, readily accessible, and with the required signage. The shut off valve installation described in keynote 9 on sheet P1.2 is not readily accessible and is not located adjacent to the egress door. Reference: Section 409.6, IFGC 2012.
06/13/2016 ROBERT SHERRY WATER REVIEW Completed
06/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The portion of the building shell being modified in this activity does not appear to have been conditioned. Section C101.4.5, IECC 2012 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2012) is to be accomplished. Reference: Section C401.2, IECC 2012.
3. Revise the heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.
4. Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012.
5. The three AC units are not located in the same locations as those shown on the structural drawings for the shell building. Provide structural calculations to verify that the new roof top AC units will be safely supported by the building structure. Reference: Section 302.1, IMC 2012.
6. Show the size, routing, and termination of the condensate drains from the rooftop AC units. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
7. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012.
8. Provide an air balancing report prior to the final mechanical inspection to verify that the HVAC systems are capable of supplying and exhausting at least the minimum air flow rates called for in the design drawings. The balancing shall be performed by a qualified balancing contractor in accordance with the procedural standards of either the National Environmental Balancing Bureau (NEBB) or the Associated Air Balance Council (AABC). Reference: Section 403.7, IMC 2012.
9. Revise the mechanical design as required to avoid using the egress corridors as return air ducts. Reference: Section 601.2, IMC 2012.
06/16/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1.0; ACCESSIBILITY: THE DRAWING STATES THERE ARE TWO ACCESSIBLE EXITS AND ONE ACCESSIBLE ENTRANCE. PLEASE CLARIFY.
2. SHEET T1.0; PLLUMBING FIXTURE COUNT: FOR THE LAVATORIES, PLEASE INDICATE ONE IS REQUIRED IN THE MEN'S AND ONE IS REQUIRED IN THE WOMEN'S.
3. SHEET T2.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
4. SHEET A1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
5. SHEET A1.1; FLOOR PLAN KEYNOTES: NOTE 15 INDICATES A BOTTLE FILLING STATION. THE DETAIL 5/A5.2 AND SHEET P4.0 DO NOT INDICATE BOTTLES OR CUPS LOCATED FOR ACCESSIBLE USE WITH THIS STATION. PLEASE PROVIDE ON THE DRAWINGS.
6. SHEET A1.1; KEYNOTE 31: A DETAIL REFERENCE ON THE EAST END OF THIS RAIL (IN ROOM 124) INDICATES 3/A5.1. PLEASE REVISE THIS REFERENCE NUMBER.
7. SHEET A1.1; PARTITION TYPES A AND B: PLEASE INDICATE THE SIZE AND QUANTITY OF CONNECTORS FOR THE DIAGONAL BRACING AT THE ROOF STRUCTURE AND TO THE TOP OF THE PARTITION, OR REFERENCE THE STRUCTURAL DETAILS ON SHEET S1.1.
8. SHEET A7.1; REFLECTED CEILING PLAN: A NOTE IN THE NORTHWEST CORNER OF THE PLAN REFERENCES DETAIL 10/S1.1 FOR A SATELLITE SUPPORT PIPE. PLEASE REVISE THE DETAIL REFERENCE NUMBER.
9. GENERAL: THE SEALS OF THE REGISTERED DESIGN PROFESSIONALS ON THE DRAWINGS MUST INDICATE THE DATE THE SEAL WAS SIGNED, AND THE EXPIRATION DATE OF THE REGISTRANT'S LICENSE.
10. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/21/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved