Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T-1; DESIGN CODES: PLEASE REMOVE THE 2012 IRC AND ADD THE 2009 ICC/ANSI A117.1 ACCESSIBILITY CODE.
2. SHEET T-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CODE REVIEW AND BUILDING DATA.
3. SHEET T-1; CODE REVIEW: PLEASE INCLUDE THE PATIO SQUARE FOOTAGE ON THE DRAWING.
4. SHEETS D-1, A-1, A-2, A-3, AND A-4: PLEASE PROVIDE A NORTH ARROW ON THE PLANS.
5. SHEET A-1; FLOOR PLAN: RESTROOM 105 CAN NOT BE REFERENCED AS A HANDICAP ACCESSIBLE ROOM. THE CLEARANCE FOR THE WATER CLOSET DOES NOT MEET THE ICC/ANSI REQUIREMENT (SEE FIGURE 604.3). PLEASE REMOVE THE HANDICAP DESIGNATION ON THE PLAN.
6. SHEET A-1; ACCESSIBILITY NOTES: NOTE 2D DOES NOT INDICATE A VERTICAL GRAB BAR AS REQUIRED BY THE ICC/ANSI FIGURE 604.5.1. PLEASE ADD.
7. SHEET A-1: PLEASE INDICATE ON THIS SHEET THE COST OF THE ACCESSIBILITY UPDATES IN THIS PROJECT, AND INDICATE THE PERCENTAGE THIS COST REPRESENTS AS COMPARED TO THE TOTAL PROJECT COSTS. SEE THE IBC SECTION 3411.7.
8. SHEET A-2; FLOOR PLAN: PLEASE INDICATE ON THIS SHEET THE CALCULATION FOR THE NUMBER OF REQUIRED ACCESSIBLE DINING SURFACES/SEATING PER THE IBC SECTION 1108.2.9.1. INDICATE THOSE ON THE FLOOR PLAN. ONE TABLE WAS INDICATED ON THE PLAN.
9. SHEET A-6; REAR ELEVATION: AN ENLARGED DETAIL IS REFERENCED AS 4/A-9. PLEASE REVISE THAT REFERENCE.
10. SHEET A-12; DOOR SCHEDULE: PLEASE PROVIDE DOOR HARDWARE ON THIS SHEET FOR ALL DOORS.
11. SHEET A-12: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NATIONAL ACCOUNT INFORMATION.
12. SHEET S-2; FOUNDATION PLAN: PLEASE PROVIDE A NORTH ARROW ON THE PLAN.
13. SHEET S-3; ROOF FRAMING PLAN: PLEASE PROVIDE A NORTH ARROW ON THE PLAN.
14. SHEET S-4; DETAILS 401, 402, 403, 404, 406, AND 407: PLEASE INDICATE ON THESE DETAILS TO REFERENCE SHEET A-1 FOR WALL DIMENSIONS/LOCATIONS (FOR FOUNDATION PURPOSES).
15. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/23/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 5346 E. 22nd Street
T16CM04030
Building Plan (1st Review)

TRANSMITTAL DATE: June 23, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans have been reviewed and it appears that the building plan match development package DP16-0090. But until Dp16-0090 has been approved Zoning will not approve.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956