Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM03867
Parcel: 10408095C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03867
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Keynote 3 on sheet C-AR102 refers to the plumbing drawings for the dimensions of the gutter and downspouts for the canopy. Provide the dimensions of the gutter and downspouts. Reference: Section 106.1.1, IBC 2006.
2. Detail 1/C-PL021 shows the installation of a hose bibb at the base of a light pole. Where does this occur (i.e. how many locations)? Reference: Section 106.1.1, IBC 2006.
07/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/29/2016 ROBERT SHERRY WATER REVIEW Completed
08/01/2016 MARTIN BROWN FIRE REVIEW Approved
08/12/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Percision Toyota
T16CM03867
Building Plan (1st Review)

TRANSMITTAL DATE: August 12, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until the revisions to development package DP12-0181 have been approved Zoning cannot approve the building plan.

3. All site sheets provided in the building plan need to be marked for reference only or removed from the set. If the site sheets remain all details should match what is shown on the development package, i.e. accessible sign mounting height.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
08/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET GI002; CODE ANALYSIS: THE TOTAL ALLOWABLE SQUARE FOOTAGE LISTED IN THE TABLE (80,040 SF) DOES NOT MATCH THE CALCULATION SHOWN BELOW THE TABLE (86,250 SF). PLEASE COORDINATE.
2. SHEET GI002; CODE ANALYSIS: PLEASE LIST THE ACTUAL SQUARE FOOTAGE OF THE EXISTING NEW CAR SALE BUILDING PLUS THE NEW CANOPY IN THIS ANALYSIS.
3. SHEET GI002; BUILDING DATA: PLEASE VERIFY THE ACTUAL SQUARE FOOTAGE OF THE CANOPY FOR THIS PERMIT. THIS SHEET INDICATES 8123 SF.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/16/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a complete luminaire schedule for all the types of luminaires used for this phase and identify all luminaires shown on the plans. Include the canopy (display) lighting.
#2. Ref: TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE.
(A). Verify that all areas shown qualify as special use (outdoor sales), as stated on the Outdoor Lighting Calc's, such as the display, or canopy areas. If not, provide compliance with chapter 4 as stated in sec. 701.2
(B). Provide or indicate on the plans, details for automatic lighting controls as required per sec.701.4 and 403.4, 403.5.
(C). A special inspection will be required per sec. 106.2.3.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements, Tucson Outdoor Lighting Code.