Permit Number: T16CM03860
Parcel: 105110690

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03860
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2016 ANDREW CONNOR ZONING REVIEW Approved
05/24/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide coolig/heating load calculations.
2. Provide ventilation calculations for the suite.
3. Show that the selected heat pump and thermostat meet the requirements of the 2012 IECC.
05/24/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/24/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
05/24/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/24/2016 ROBERT SHERRY WATER REVIEW Reqs Change Verify the size of the water meter serving this suite.
05/24/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory that dispenses 0.25 gallons per cycle with each cycle lasting at least 10 seconds.
2. Verify the capacity of the water heater.
3. Provide a pressure regulator for the water service if one is not already in place to limit the pressure to less than 80 PSI.
05/24/2016 KEN BROUILLETTE FIRE REVIEW Approved
05/24/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2016 ARUIZ1 OUT TO CUSTOMER Completed