Permit Number: T16CM03842
Parcel: 11516024A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03842
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2016 LOREN MAKUS ENGINEERING REVIEW Approved
05/24/2016 ANDREW CONNOR ZONING REVIEW Approved
05/24/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the new heat pumps, N1A and N2A.
2. Clarify the outdoor air calculation that refers to HP-1 only.
05/24/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/24/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change The square footage does not match on the cover sheet. Need to know the occupant load of the existing Group M occupancy. The code sheet indicates that neither separated or non-separated uses will be used.
Please provide an egress plan too.
05/24/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/24/2016 ROBERT SHERRY WATER REVIEW Completed
05/24/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/24/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed