Permit Number: T16CM03791
Parcel: 10703151C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03791
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2016 ANDREW CONNOR ZONING REVIEW Approved
05/23/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the exhaust flow rate for the fan in the men's restroom is at least equal to the new supply air flow rate into the room.
05/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Update the registrant stamp.
#2. Indicate all feeder conduit and conductor sizes and types for new and re-fed electrical equipment. Verify OCPD devices and feeders shown for panel 'b' seems to be undersized.
Ref: 2012 IBC sec.107.2.1, 2011 NEC
05/23/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
05/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/23/2016 ROBERT SHERRY WATER REVIEW Completed
05/23/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/23/2016 KEN BROUILLETTE FIRE REVIEW Approved
05/23/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed