Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM03791
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 05/23/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify that the exhaust flow rate for the fan in the men's restroom is at least equal to the new supply air flow rate into the room. |
| 05/23/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Update the registrant stamp. #2. Indicate all feeder conduit and conductor sizes and types for new and re-fed electrical equipment. Verify OCPD devices and feeders shown for panel 'b' seems to be undersized. Ref: 2012 IBC sec.107.2.1, 2011 NEC |
| 05/23/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 05/23/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/23/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/23/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/23/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 05/23/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |