Permit Number: T16CM03742
Parcel: 11012007B

Address:
5151 E GRANT RD

Review Status: Active

Review Details: REVISION - - 3RD

Permit Number - T16CM03742
Review Name: REVISION - - 3RD
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/05/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a plumbing design showing the work to be accomplished. Include the required increase in exhaust for the modified restroom/shower areas.
05/05/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide the following information on tha plans.
#1. Denote all the electrical equipment that is existing. New electrical equipment and devices, lighting, need to have assigned branch circuits and panel designations.
#2. Provide a complete panel schedule include load calcs.
#3. Provide a complete lighting schedule and compliance with the 2012 IECC if applicable.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC.
05/05/2017 ANY ZONING REVIEW Active