Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM03678
Parcel: 141153530

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM03678
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/03/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/03/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/03/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2016 KROBLES1 OUT TO CUSTOMER Completed