Permit Number: T16CM03636
Parcel: 115046700

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T16CM03636
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2016 ANY ZONING REVIEW Active
05/13/2016 ANY MECHANICAL-COMMERCIAL REVIEW Active
05/13/2016 ANY PLUMBING-COMMERCIAL REVIEW Active
05/13/2016 ANY ENGINEERING REVIEW Active
05/13/2016 ANY BUILDING-COMMERCIAL REVIEW Active
05/13/2016 ANY WATER REVIEW Active
05/13/2016 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
05/13/2016 ANY FIRE REVIEW Active
06/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a complete panel schedule, Include complete panel load calc's to verify added loads ( washer, dryer ) are within the capacity of the existing electrical system.
Ref; 2012 IBC 107.2.1, 2011 Nec art, 408. City of Tucson Commercial Plan Submittal Requirements.