Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T16CM03636
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2016 | ANY | ZONING | REVIEW | Active | |
| 05/13/2016 | ANY | MECHANICAL-COMMERCIAL | REVIEW | Active | |
| 05/13/2016 | ANY | PLUMBING-COMMERCIAL | REVIEW | Active | |
| 05/13/2016 | ANY | ENGINEERING | REVIEW | Active | |
| 05/13/2016 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
| 05/13/2016 | ANY | WATER | REVIEW | Active | |
| 05/13/2016 | ANY | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active | |
| 05/13/2016 | ANY | FIRE | REVIEW | Active | |
| 06/27/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a complete panel schedule, Include complete panel load calc's to verify added loads ( washer, dryer ) are within the capacity of the existing electrical system. Ref; 2012 IBC 107.2.1, 2011 Nec art, 408. City of Tucson Commercial Plan Submittal Requirements. |