Permit Number: T16CM03625
Parcel: 12801005F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03625
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL ALL SHEETS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
2. GENERAL ALL SHEETS: PLEASE DARKEN TEXT SO IT IS MORE LEGIBLE.
3. SHEET A101; FLOOR PLAN: IS THE ADDITION OF WALLS AND DOORS IN THE EXISTING DRESSING AND STOCK ROOMS BEING CONSIDERED PART OF THIS PROJECT? PLEASE VERIFY.
4. SHEET A300; SECTIONS 1 AND 2: AT THE DIAGONAL BRACING, INDICATE THE BRACING SIZE AND CONNECTIONS (QUANTITY AND SIZE) TO THE TOP OF THE PARTITION AND TO THE STRUCTURE ABOVE.
5. SHEET A400: SEE COMMENT 4.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/01/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/01/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed