Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T16CM03553
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/26/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural details showing how the shelf for the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2012. 2. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2012. 3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. 4. Provide location and sizing information for gutters and downspouts. Reference: Sections 1106.1 and 1106.6, IPC 2012. |
| 05/27/2016 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | CDCDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera for Steve Shields Principal Planner PDSD Zoning Review PROJECT: 1st and River Self Storage Building Plans (1st Review) T16CM03553 TRANSMITTAL DATE: May 27, 2016 DUE DATE: June 7, 2016 COMMENTS: Address the following zoning comments. Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Comment 1. Zoning has reviewed the building plans as it relates to the zoning review purview of the building plans such as heights, square footage, and building footprint but cannot approve them at this time. While the plans are consistent with the current version of the development package under review zoning cannot approve the building plans until the DP is approved and the building plans are reviewed and approved by the PDSD structural plans reviewer and other PDSD commercial review agencies. Comment 2. Zoning will review the building plans on the next submittal and compare them to the development package for consistency. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans as required |
| 05/27/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the ventilation calculation using the ventilation rates shown in Table 403.3, IMC 2012 (e.g. Public corridors, 0.06 CFM/SF; Retail Storage, 0.12 CFM/SF). Reference: Section 403.3, IMC 2012. 2. Secure the refrigerant circuit access ports of the ground-mounted condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2012. |
| 05/27/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/01/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | Development Package must be approved first. |
| 06/02/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET 0.0; ELEVATOR SHAFT: THE ELEVATOR SHAFT IS REQUIRED (PER THE IBC SECTION 713.14) TO BE CONSTRUCTED IN ACCORDANCE WITH SECTION 713 (PER 713.4, ONE HOUR FIRE BARRIER FOR LESS THAN FOUR STORIES). SECTION 712 (AS REFERENCED ON THESE DRAWINGS) REQUIRES APPLICATIONS LISTED IN THIS SECTION (712.1.1 SHAFT ENCLOSURES) TO HAVE FIRE RESISTANCE RATINGS. PLEASE VERIFY AND REVISE. 2. SHEET 0.0; ELEVATOR LOBBY: PER THE IBC SECTION 713.14.1, THE ELEVATOR LOBBY IS NOT REQUIRED TO BE ENCLOSED WITH A FIRE RESISTANCE RATING SINCE THE ELEVATOR SHAFT CONNECTS THREE STORIES OR LESS. PLEASE VERIFY. 3. SHEET 0.0: PER THE IBC TABLE 1108.3, PLEASE INDICATE ON THE DRAWINGS THE REQUIRED NUMBER OF ACCESSIBLE STORAGE SPACES, AND INDICATE THE LOCATIONS OF THOSE SPACES ON A PLAN. 4. SHEET 0.0: PER THE IBC SECTION 2902.3.2, PLEASE INDICATE ON THE DRAWINGS THE LOCATION OF THE TOILET FACILITIES MEETS THE REQUIREMENTS OF THAT SECTION. 5. SHEET 0.0; EXIT DISTANCE: PLEASE PROVIDE PLANS FOR THE FIRST FLOOR AND THE BASEMENT INDICATING THE EXIT ACCESS TRAVEL DISTANCE (AS MEASURED PER THE IBC SECTION 1016.3) MEETS THE REQUIREMENTS OF TABLE 1016.2 (VERIFY THE DISTANCES INDICATED ON SHEET 0.0). 6. SHEET 1.1; FLOOR PLAN KEYNOTES: THE NOTE NUMBERS CAN NOT BE READ ON THIS SHEET. PLEASE REVISE. 7. SHEET 1.1; FLOOR PLAN: PLEASE INDICATE THE LAVATORIES IN TOILET ROOMS 199 AND 200. 8. SHEET 1.1; FLOOR PLAN: IT DOES NOT APPEAR THE MANEUVERING CLEARANCE (ON THE PUSH SIDE) AT DOOR D11 MEETS THE REQUIREMENT OF THE ICC/ANSI FIGURE 404.2.3.2(b). PLEASE VERIFY. 9. SHEETS 1.1 AND 1.2; WALL LEGEND: FOR WALLS REQUIRING A FIRE RESISTANCE RATING, PLEASE INDICATE ON THE DRAWINGS THE U.L. NUMBER FOR THAT ASSEMBLY. 10. SHEETS 1.1 AND 1.2; FLOOR PLANS: PER THE IBC SECTION 3006, THE ELEVATOR EQUIPMENT ROOM B83 IN THE BASEMENT AND MECHANICAL ROOM 198 ON THE FIRST FLOOR MUST BE ENCLOSED BY FIRE BARRIERS (SECTION 707) OR HORIZONTAL ASSEMBLIES (SECTION 711) OR BOTH. INDICATE ON THE DRAWINGS THESE ROOMS MEET THOSE REQUIREMENTS FOR FIRE RESISTANCE RATED CONSTRUCTION PER THE IBC SECTION 3006.4. 11. SHEET 1.3; DOOR SCHEDULE: PLEASE REVISE THE DOOR SCHEDULE BY ADDING RATED DOORS LOCATED IN FIRE RESISTANCE RATED WALL ASSEMBLIES. 12. SHEET 1.3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 13. SHEET 1.3 (DETAIL 13); SHEET S4.2 (DETAIL 222): PLEASE COORDINATE THESE DETAILS. 14. SHEET 1.5: PLEASE REVISE THE SHEET TITLE. 15. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE SIGNAGE REQUIREMENTS OF THE IBC SECTION 2902.4 AND THE DIRECTIONAL SIGNAGE REQUIREMENTS OF SECTION 2902.4.1 ARE MET. 16. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE DRINKING FOUNTAIN LOCATION REQUIREMENTS OF THE IBC SECTION 2902.5 ARE MET. 17. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE PENETRATIONS INTO OR THROUGH FIRE RESISTANCE RATED WALLS MEET THE REQUIREMENTS OF THE IBC SECTION 714.3. 18. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE JOINT SYSTEMS IN OR BETWEEN FIRE RESISTANCE RATED WALLS MEET THE REQUIREMENTS OF THE IBC SECTION 715. 19. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE MEANS OF EGRESS ILLUMINATION MEETS THE REQUIREMENTS OF THE IBC SECTION 1006. 20. GENERAL: PLEASE INDICATE ON THE DRAWINGS IF THE STAIRWAYS ARE CONSIDERED TO BE PART OF AN ACCESSIBLE MEANS OF EGRESS. IF SO, VERIFY THE REQUIREMENTS OF THE IBC SECTIONS 1007.3 AND 1009.8 ARE MET. 21. GENERAL: PLEASE INDICATE ON THE DRAWINGS IF THE ELEVATOR IS CONSIDERED TO BE PART OF AN ACCESSIBLE MEANS OF EGRESS. IF SO, VERIFY THE REQUIREMENTS OF THE IBC SECTION 1007.4 ARE MET. 22. GENERAL: PLEASE INDICATE ON THE DRAWINGS IF THE TWO WAY COMMUNICATION SYSTEM MEETS THE REQUIREMENTS OF THE IBC SECTION 1007.8. 23. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTIONS 1007.9 AND 1007.10 FOR SIGNAGE AND DIRECTIONAL SIGNAGE ARE MET. 24. STRUCTURAL CALCULATIONS: PLEASE PROVIDE REFERENCE (KEY) PLANS IN THE CALCULATIONS LOCATING THE STRUCTURAL MEMBERS (JOISTS, BEAMS, COLUMNS, LINTELS, STUDS, FOOTIINGS, SHEARWALLS, ETC.) AS DESIGNED. 25. GENERAL: PAGE 15 OF THE STRUCTURAL CALCULATIONS INDICATES PHOTOVOLTAIC MODULES ARE TO BE INSTALLED ON THIS ROOF SYSTEM. THERE WAS NO INDICATION AT THE TIME OF THE PROJECT SUBMITTAL THAT THIS PROJECT INCLUDED ANY PHOTOVOLTAIC MODULES. PLEASE VERIFY. 26. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 06/03/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 06/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |