Permit Number: T16CM03436
Parcel: 12410504A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03436
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2016 MARTIN BROWN FIRE REVIEW Approved
06/06/2016 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T16CM03436 PERMIT REVIEW COMMENTS
Reviewer: Christopher Anderson, June 6, 2016
SHEET T1
1. The Arizona Board of Technical Registration requires that the professional seal on each document bear the sealing date and the expiration date of the seal.
2. Add suite number to title.
SHEET A1
1. Interior Signage Schedule, item 137 should read "Medical Gases NO Smoking or Open Flame" per NFPA 99 5.1.3.1.9.
SHEET A2
1. 2012 IBC Table 509 requires that waste and linen rooms in ambulatory care facilities be enclosed with 1-hour fire-rated wall assemblies. Soiled Holding 127 and Medical Trash 134 appear to require 1-hour fire-rated enclosure.
2. With open grilles for direct outside air ventilation and with no mechanical space conditioning, insulate Oxygen 137 walls with R-13 minimum insulation and provide door with U-factor of 0.61 per 2012 IECC table C402.2.
SHEET A3
1. New aluminum and glass entry 110 and window wall shall meet the following requirements per 2012 IECC Table C402.3:
a. New glazed entry: U-factor = 0.83 and SHGC = 0.25
b. New fixed window wall: U-factor = 0.50 and SHGC = 0.25
SHEET A4
1. Door 101a and hardware set A do not exist on floor plan.
2. Per 2012 IBC 1008.1.9 egress doors shall be readily openable from the egress side without the use of a key or special knowledge. Add this note to door 110.
3. Verify 45 minute fire rated door sufficient for 1 hour assembly
SHEET A6
1. Oxygen & Vacuum System Note 6C shall refer to the 2012 IFC and the 2012 NFPA 99.
06/06/2016 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change SHEET M8
1. Per COT amendment to the 2012 IPC, 416.6 requires that all lavatories be provided with automatic faucets dispensing maximum 0.25 gallon per metering cycle.
2. Justify water line size to clinical sink according to the proposed flow rate.
06/06/2016 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change SHEET E4
1. Please explain the discrepancy between Fault Current Calculation for X1 with required wire size 500 KCMIL and Power Riser Diagram which shows wire size for X1 as 350 KCMIL.
06/06/2016 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change SHEET M1
1. General Note 12 requires structural "signoff" for new rooftop units on the existing roof. Submit structural calculations sealed by an Arizona structural engineer analyzing the existing roof structure capacity to accommodate new HVAC roof loads.
SHEETS M2 & M3
1. Add fire dampers at rooms 127 and 134. See SHEET A2, note 1 above.
SHEET M4
1. Indicate water meter size and submit water calculations. Will existing meter be used for both tenant spaces?
SHEET M5
1. Because existing sanitary and venting layout has not been ascertained it is likely that the proposed layout for the new facility will need to be modified. If the configuration of the sanitary lines must be changed to accommodate actual locations of existing sanitary lines, submit a revised plan (and riser diagrams) to the City of Tucson as a Revision prior to installation. Add this note to the sheet.
SHEET M8
1. Per COT amendment to the 2012 IPC, 416.6 requires that all lavatories be provided with automatic faucets dispensing maximum 0.25 gallon per metering cycle.
2. Provide load calculations to justify the heating and cooling capacities of the equipment specified. 2012 IECC C403.2.2 and 2012 IMC 312.1.
06/10/2016 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size of the water meter serving this building and determine the total demand served by the meter. Reference: Section 107.2.1, IBC 2012.
2. Revise the site utility plan to show the location of the reduced pressure backflow assembly and indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf