Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM03374
Parcel: 12212010B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03374
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2016 ANDREW CONNOR ZONING REVIEW Approved
05/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The minimum font size shall be 3/32" (e.g. the refrigeration design)
05/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please coordinate the OCPD for the new panel 'H' 150 AMP panel as required per 2011 NEC art. 408.36
05/05/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
05/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/05/2016 ROBERT SHERRY WATER REVIEW Completed
05/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show that the existing natural gas distribution system is capable of adding the new oven without causing the existing system to be overloaded.
2. All directly-connected beverage dispensers shall be protected with a backflow protector that is listed to ASSE 1022.
3. The natural gas supplier, Southwest Gas, delivers gas with 1000 BTU per cubic foot.
4. the minimum font size is 3/32".
05/05/2016 KEN BROUILLETTE FIRE REVIEW Approved
05/05/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2016 KROBLES1 OUT TO CUSTOMER Completed