Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM03374
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/05/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
05/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The minimum font size shall be 3/32" (e.g. the refrigeration design) |
05/05/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please coordinate the OCPD for the new panel 'H' 150 AMP panel as required per 2011 NEC art. 408.36 |
05/05/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
05/05/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/05/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/05/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show that the existing natural gas distribution system is capable of adding the new oven without causing the existing system to be overloaded. 2. All directly-connected beverage dispensers shall be protected with a backflow protector that is listed to ASSE 1022. 3. The natural gas supplier, Southwest Gas, delivers gas with 1000 BTU per cubic foot. 4. the minimum font size is 3/32". |
05/05/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
05/05/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/31/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |