Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM03297
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/29/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved. [Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.] 2. Comment not resolved. [Initial comment: The specified temperature mixing valve is listed as conforming to ASSE 1070 as well as ASSE 1016. Revise the specifications to note the correct standard, ASSE 1070, so that an incorrect mixing valve is not substituted. Reference: Sections 416.5 and 607.1.2, IPC 2012.] 3. Comment not resolved. [Initial comment: Revise the water demand estimate by including the continuous demand from the evaporative coolers. Reference: Section A 2.2, UPC 2012.] 4. The proposed storage-type water heater requires the installation of an expansion tank. [Initial comment: The proposed instantaneous water heater has a minimum activation rate of 0.5 GPM but the total flow rate (cold water plus hot water) for the lavatory faucet is also 0.5 GPM. Verify that the proposed water heaters will be able to provide tepid water for the lavatories. Reference: Section 607.1, IPC 2012.] 5. Comment not resolved. [Initial comment: Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012.] |
06/29/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/01/2016 | RBENT1 | ZONING | REVIEW | Needs Review | |
07/01/2016 | RBENT1 | ENGINEERING | REVIEW | Needs Review |