Permit Number: T16CM03297
Parcel: 14117009B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM03297
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. [Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]
2. Comment not resolved. [Initial comment: The specified temperature mixing valve is listed as conforming to ASSE 1070 as well as ASSE 1016. Revise the specifications to note the correct standard, ASSE 1070, so that an incorrect mixing valve is not substituted. Reference: Sections 416.5 and 607.1.2, IPC 2012.]
3. Comment not resolved. [Initial comment: Revise the water demand estimate by including the continuous demand from the evaporative coolers. Reference: Section A 2.2, UPC 2012.]
4. The proposed storage-type water heater requires the installation of an expansion tank. [Initial comment: The proposed instantaneous water heater has a minimum activation rate of 0.5 GPM but the total flow rate (cold water plus hot water) for the lavatory faucet is also 0.5 GPM. Verify that the proposed water heaters will be able to provide tepid water for the lavatories. Reference: Section 607.1, IPC 2012.]
5. Comment not resolved. [Initial comment: Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012.]
06/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/01/2016 RBENT1 ZONING REVIEW Needs Review
07/01/2016 RBENT1 ENGINEERING REVIEW Needs Review