Permit Number: T16CM03297
Parcel: 14117009B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM03297
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2016 MARTIN BROWN FIRE REVIEW Approved
06/08/2016 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera for Steve Shields
PDSD Zoning Review

PROJECT: Produce Warehouse
Building Review
T16CM03297 Related to DP16-0075

TRANSMITTAL DATE: June 8, 2016

DUE DATE: June 29, 2016

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Zoning has reviewed the building plans as it relates to the zoning review purview. While the building plans are consistent with the zoning DP Zoning cannot approve the building plans until the DP is approved. The T.I. cannot be approved until the Shell or Building plans are approved.
06/08/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Can not be approved until DP 16-0075 is approved.
06/16/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the outer circle of the registrant's seal shall be 1-1/2" in diameter, +/- 1/16". See Appendix A of the Rules of the Arizona State Board of Technical Registration for further information regarding seals.
2. Direct reuse of reclaimed water (i.e. grey water) from a non-residential source requires a permit from the State of Arizona Department of Environmental Quality.
3. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2012, for storage occupancy (e.g. service sink and two drinking fountains).
4. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
5. The specified temperature mixing valve is listed as conforming to ASSE 1070 as well as ASSE 1016. Revise the specifications to note the correct standard, ASSE 1070, so that an incorrect mixing valve is not substituted. Reference: Sections 416.5 and 607.1.2, IPC 2012.
6. Revise the water demand estimate by including the continuous demand from the evaporative coolers. Reference: Section A 2.2, UPC 2012.
7. The proposed instantaneous water heater has a minimum activation rate of 0.5 GPM but the total flow rate (cold water plus hot water) for the lavatory faucet is also 0.5 GPM. Verify that the proposed water heaters will be able to provide tepid water for the lavatories. Reference: Section 607.1, IPC 2012.
8. Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012.
06/16/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the outer circle of the registrant's seal shall be 1-1/2" in diameter, +/- 1/16". See Appendix A of the Rules of the Arizona State Board of Technical Registration for further information regarding seals.
2. Clarify the number of evaporative coolers to be used; the architectural roof plan appears to show eight units. Reference: Section 107.2.1, IBC 2012.
06/16/2016 ROBERT SHERRY WATER REVIEW Completed
06/29/2016 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Completed
06/29/2016 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2016 RBENT1 OUT TO CUSTOMER Completed