Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM03275
Parcel: 11108136A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03275
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2016 ANDREW CONNOR ZONING REVIEW Approved
05/04/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the SHGC for the fenestration in the new residential areas per Table R402.1.1, IECC 2012. All fenestration shall be NFRC-certified. Reference: Sections C101.4.6 and C303.1.3, IECC 2012.
2. Show that the exterior walls for the office and laundry room comply with the requiewments of Table C402.2 for insulation.
3. Revise the air distribution to avoid using the corridor as a duct. Reference: Section 601.2, IMC 2012.
05/04/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please designate circuits and panels for all new electrical devices and equipment. Include conductor types and sizes for branch circuits and feeders. Also provide complete panel schedules.
Ref: IBC sec 107.2.1, NEC art. 408.4.
05/04/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
05/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE TWO ADDITIONS TO THE EXISTING BUILDING. INCLUDE THE REVIEW OF THE NEW ROOF MECHANICAL UNITS TO ENSURE THE EXISTING TRUSSES CAN SAFELY SUPPORT THE NEW LOADS.
2. SHEET A6: PLEASE PROVIDE GRAB BAR AND CONTROL LOCATIONS FOR THE TRANSFER TYPE SHOWER. USE THE ICC/ANSI A117.1 SECTION 608.
05/04/2016 ROBERT SHERRY WATER REVIEW Completed
05/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide fixture descriptions for all plumbing fixtures. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012.
2. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2012.
3. Coordinate details 1/P-2.1 and 202.
4. The plumbing schedule remarks column for P-5 calls for a floor sink; where is it?
5. Clarify which water pipe sizing is being used; IPC, UPC, or other?
05/04/2016 MARTIN BROWN FIRE REVIEW Approved
05/04/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2016 ARUIZ1 OUT TO CUSTOMER Completed