Review Details: COMMERCIAL - TI

Permit Number - T16CM03160
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2016 MARTIN BROWN FIRE REVIEW Approved
05/09/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the material standards for the water distribution piping materials and fittings. Reference: Sections 605.3 and 605.5, IPC 2012.
2. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
3. Specify the materials to be used for the drainage piping and fittings. Reference: Section 702, IPC 2012.
05/09/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide structural calculations and details to demonstrate that the installation of the two new computer room AC units will not adversely affect the structure. Reference: Section 302.1, IMC 2012.
05/09/2016 ROBERT SHERRY WATER REVIEW Completed
05/18/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; INTERIOR PARTITION 1: PLEASE INDICATE THE BRACING SIZE AND HOW IT IS ATTACHED (SIZE AND QUANTITY OF CONNECTORS) TO THE TOP OF THE PARTITION AND TO THE STRUCTURE ABOVE. PLEASE INCLUDE A DETAIL OF THE STRUCTURE ABOVE AND HOW THE BRACE IS CONNECTED ALONG WITH ANY ADDITIONAL FRAMING MEMBERS.
05/20/2016 STEVE SHIELDS ZONING REVIEW Approved
05/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the 2012 IECC for interior lighting. Ref: 2012 IECC.
05/25/2016 LOREN MAKUS ENGINEERING REVIEW Approved