Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM03136
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/01/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. STRUCTURAL DRAWINGS/CALCULATIONS: THE LICENSED PROFESSIONAL ENGINEER OF RECORD MUST INCLUDE HIS PROFESSIONAL SEAL, SIGNATURE, CURRENT DATE, AND PROFESSIONAL LICENSE EXPIRATION DATE ON EACH SHEET. PLEASE PROVIDE. 2. STRUCTURAL DRAWINGS/CALCULATIONS; SHEET 1/1: PLEASE INDICATE ON THE DRAWINGS HOW THE 12 PSF ROOF LIVE LOAD WAS DETERMINED. 3. STRUCTURAL DRAWINGS/CALCULATIONS; SHEET 1/1: THE BASIC ULTIMATE DESIGN WIND SPEED PER THE IBC FIGURE 1609A IS 115 MPH. PLEASE REVISE NOTE AND CALCULATIONS AS REQUIRED. 4. STRUCTURAL DRAWINGS/CALCULATIONS; SHEET 1/1: PLEASE INDICATE ON THE DRAWINGS HOW THE SOIL RESISTIVE/BEARING VALUES WERE DETERMINED (SEE FOUNDATION NOTES ON SHEET 1/1). 5. GENERAL: PLEASE PROVIDE INFORMATION AND CALCULATIONS ON THE 'SKIN' COVERING THIS STEEL STRUCTURE (ALLOWABLE STRESSES, ACTUAL STRESSES, CONNECTIONS TO STRUCTURE, ETC.). 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/09/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |