Permit Number: T16CM03136
Parcel: 141030260

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM03136
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. STRUCTURAL DRAWINGS/CALCULATIONS: THE LICENSED PROFESSIONAL ENGINEER OF RECORD MUST INCLUDE HIS PROFESSIONAL SEAL, SIGNATURE, CURRENT DATE, AND PROFESSIONAL LICENSE EXPIRATION DATE ON EACH SHEET. PLEASE PROVIDE.
2. STRUCTURAL DRAWINGS/CALCULATIONS; SHEET 1/1: PLEASE INDICATE ON THE DRAWINGS HOW THE 12 PSF ROOF LIVE LOAD WAS DETERMINED.
3. STRUCTURAL DRAWINGS/CALCULATIONS; SHEET 1/1: THE BASIC ULTIMATE DESIGN WIND SPEED PER THE IBC FIGURE 1609A IS 115 MPH. PLEASE REVISE NOTE AND CALCULATIONS AS REQUIRED.
4. STRUCTURAL DRAWINGS/CALCULATIONS; SHEET 1/1: PLEASE INDICATE ON THE DRAWINGS HOW THE SOIL RESISTIVE/BEARING VALUES WERE DETERMINED (SEE FOUNDATION NOTES ON SHEET 1/1).
5. GENERAL: PLEASE PROVIDE INFORMATION AND CALCULATIONS ON THE 'SKIN' COVERING THIS STEEL STRUCTURE (ALLOWABLE STRESSES, ACTUAL STRESSES, CONNECTIONS TO STRUCTURE, ETC.).
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2016 KROBLES1 OUT TO CUSTOMER Completed