Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM03134
Parcel: 11712098A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM03134
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide HVAC drawings that indicate the extent of work to be done as part of this activity. Reference: Section 107.2.1, IBC 2012.
04/29/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
04/29/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please designate circuiting and panels for the new receptacles, also provide a complete panel schedule and location of the panel assigned.
Ref: 2012 IBC 107.2.1
04/29/2016 ANDREW CONNOR ZONING REVIEW Approved
04/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/29/2016 ROBERT SHERRY WATER REVIEW Approved
04/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/03/2016 MARTIN BROWN FIRE REVIEW Approved