Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM03082
Parcel: 12411021E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM03082
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The new specification calls for the faucet to have a 7.5-second operationg cycle which does not comply with the acessibility requirements. {Second comment: The specification for the automatic faucet does not indicate that the faucet will deliver a maximum of 0.25 gallons per cycle and operate for a minimum of 10 seconds per cycle.}
[Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]