Review Details: RESUBMITTAL

Permit Number - T16CM03082
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The new specification calls for the faucet to have a 7.5-second operationg cycle which does not comply with the acessibility requirements. {Second comment: The specification for the automatic faucet does not indicate that the faucet will deliver a maximum of 0.25 gallons per cycle and operate for a minimum of 10 seconds per cycle.}
[Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]